| General | |
|---|---|
| Device category | Ceiling-mounted presence detector |
| Product information | Please note the Explanation of circuit breaker in the download area of the product! |
| Remote controllable | |
| Conformity | CE, EAC, RoHS, WEEE |
| Mounting | |
|---|---|
| Installation type | Flush-mounted/Device socket Ø 68 mm |
| Installation position | Ceiling |
| Installation dimension | Installation depth: 41 mm, Ø 60 mm |
| Type of connection | Push terminal |
| Connectable wire cross section | 1.5 mm² |
| Housing | |
|---|---|
| Dimensions | Height 87 mm, Ø 108 mm |
| Weight | 173 g |
| Material | UV-stabilised polycarbonate |
| Protection type | IP20 |
| Permissible ambient temperature | -25 °C...+50 °C |
| Relative humidity | 5 – 93 %, non-condensing |
| Colour | white, similar to RAL 9010 |
| Electrical version | |
|---|---|
| Control system | 1 – 10 V |
| Protection class | II |
| Nominal voltage | 230 V ~ / 50 Hz |
| In-rush current | 800 A / 200 µs |
| Power consumption | 0.3 W |
| Sensors | |
|---|---|
| Detection angle | 360° |
| Detection range diagonally | Ø 24 m |
| Detection range head-on | Ø {Reference (AttributeDefinition) not found: pattr8308266635517} |
| Detection range presence | Ø 8 m |
| Field of detection | up to 453 m² |
| Recommended installation height | 3 m |
| Max. mounting height | 5 m |
| Level of brightness | 5 - 2000 lx |
| Control | |
|---|---|
| Channel 2 | Lighting |
| Function | Switching |
| Number of light channels | 2 |
| Output | Switching/Dimming |
| Channel 3 | HVAC |
| Number of HVAC-channels | 1 |
| Contact | make contact / non-floating |
| output | Switching |
| Contact | make contact / floating |
| Push button input lighting | 2 |
| Switching capacity channel 2 |
230 V/50 Hz 2300 W/10 A (cos phi = 1) 1150 VA/5 A (cos phi = 0,5) 600 W LED |
| Push button input HVAC | |
| Switching capacity channel 3 |
230 V/50 Hz 2300 W/10 A (cos phi = 1) 1150 VA/5 A (cos phi = 0,5) 600 W LED |
| Master/slave function | |
| Control output | 1 - 10 V DC / 50 mA |
| Push button input channel 2 | |
| Push button input | |
| Slave input | |
| Manual override | yes |
| Time setting channel 3 | approx. 1 minute – 30 minutes |
| Max. number of slave detectors | 10 |
| Mode | Semi-automatic, Fully automatic |
| Switch-off delay channel 1 | 60 s - 30 min |
| Switching delay from "dark to light" | 300 s |
| Orientation light | 10 – 40 % luminous efficiency |
| Switch-off delay channel 2 | 60 s - 30 min |
| Switching delay from "light to dark" | 30 s |
| Switch-off delay time, orientation light | approx. 1 min.-60 min. |
| Constant light control | |
| Channels (lighting / HVAC): C1 Lighting | |
|---|---|
| Channel | C1 Lighting |
| Function | Switching, Regulate, Dimming |
| Switching capacity |
230 V/50 Hz 2300 W/10 A (cos phi = 1) 1150 VA/5 A (cos phi = 0,5) 600 W LED |
| Switch contact | make contact / non-floating |
| Push button input | |
| Impulse mode | |
| Switch-off delay time | 60 s...30 min (adjustable in steps) |
| Orientation light | 10 – 40 % luminous efficiency |
| Switch-off delay time, orientation light | 60 s...60 min |
| Channels (lighting / HVAC): C2 Lighting | |
|---|---|
| Channel | C2 Lighting |
| Function | Switching, Regulate, Dimming |
| Switching capacity |
230 V/50 Hz 2300 W/10 A (cos phi = 1) 1150 VA/5 A (cos phi = 0,5) 600 W LED |
| Switch contact | make contact / non-floating |
| Push button input | |
| Impulse mode | |
| Switch-off delay time | 60 s...30 min (adjustable in steps) |
| Orientation light | 10 – 40 % luminous efficiency |
| Switch-off delay time, orientation light | 60 s...60 min |
| Channels (lighting / HVAC): C3 HVAC | |
|---|---|
| Channel | C3 HVAC |
| Function | Switching |
| Push button input | |
| Switch-off delay time | 60 s...30 min (adjustable in steps) |
| Installation | ||
|---|---|---|
| Operating instructions | /products/a/archiv/compact/ep10426742/download/op/ep10426742_op.pdf | |
| Short instruction | /products/a/archiv/compact/ep10426742/download/ma/ep10426742_ma.pdf | |