Offers special product features like
| General | |
|---|---|
| Device category | Ceiling-mounted presence detector |
| Included in delivery | Includes lens mask |
| Remote controllable | |
| Conformity | CE, EAC, RoHS, WEEE |
| EU Data-Act betroffen | |
| Warranty | 5 years |
| Mounting | |
|---|---|
| Installation type | Flush-mounted/Device socket Ø 68 mm |
| Installation position | Ceiling |
| Type of connection | Push terminal |
| Connectable wire cross section | 0.6 – 0.8 mm² |
| Housing | |
|---|---|
| Dimensions | Height 62 mm, Ø 108 mm |
| Weight | 126 g |
| Material | UV-stabilised polycarbonate |
| Protection type | IP20 |
| Permissible ambient temperature | -25 °C...+50 °C |
| Relative humidity | 5 – 93 %, non-condensing |
| Colour | white, similar to RAL 9010 |
| Electrical version | |
|---|---|
| Control system | KNX |
| Protection class | III |
| Nominal voltage | 29 – 31 V DC |
| Power consumption | 0.2 W |
| Power consumption | 6 mA |
| Stand-by consumption | < 0.3 W |
| Sensors | |
|---|---|
| Detection angle | 360° |
| Detection range diagonally | Ø 8 m |
| Detection range head-on | Ø 6 m |
| Detection range presence | Ø 4 m |
| Field of detection | up to 50 m² |
| Recommended installation height | 3 m |
| Max. mounting height | 5 m |
| Level of brightness | 5 – 2000 lx |
| Control | |
|---|---|
| Number of light channels | 2 |
| Number of HVAC-channels | 1 |
| Push button input lighting | 2 |
| Push button input HVAC | |
| Slave input | |
| Mode | Semi-automatic, Fully automatic |
| Switching delay from "dark to light" | 300 s |
| Switching delay from "light to dark" | 30 s |
| Constant light control | |
| Sensitivity configurable | |
| KNX input | manual light control, block objects, reset, slave |
| KNX output | presence, status, light value, HVAC |
| KNX functions | Presence simulation, Constant lighting control, Manual override, Master- / slave-toiminto, Night-light feature, Sensitivity configurable, Sends a telegram at regular intervals |
| Channels (lighting / HVAC): C1 Lighting | |
|---|---|
| Channel | C1 Lighting |
| Function | Switching, Regulate |
| Switch contact | Bus system |
| Switch-off delay time | 30 s...720 min (adjustable in steps) |
| Orientation light | disabled/10 – 50 %, 2 values can be selected |
| Switch-off delay time, orientation light | 60 s...250 min |
| Channels (lighting / HVAC): C2 Lighting | |
|---|---|
| Channel | C2 Lighting |
| Function | Switching, Regulate |
| Offset setting | c2 offset from c1 (-100 % to +100 %) |
| Switch contact | Bus system |
| Switch-off delay time | 10 s...60 min (adjustable in steps) |
| Orientation light | disabled/10 – 50 %, 2 values can be selected |
| Switch-off delay time, orientation light | 60 s...250 min |
| Channels (lighting / HVAC): C3 HVAC | |
|---|---|
| Channel | C3 HVAC |
| Function | Switching |
| Switch contact | Bus system |
| Switch-on delay | 120 s...30 min |
| Switch-off delay time | 60 s...720 min (adjustable in steps) |
| Light and building planning | ||
|---|---|---|
Planning data BIM | ||