| General | |
|---|---|
| Device category | Wall-mounted presence detector |
| Remote controllable | |
| Conformity | CE, EAC, RoHS, WEEE |
| EU Data-Act betroffen | |
| Warranty | 5 years |
| Mounting | |
|---|---|
| Installation type | Flush-mounted/Device socket Ø 68 mm |
| Installation position | Wall |
| Type of connection | Push terminal |
| Connectable wire cross section | 0.6 – 0.8 mm² |
| Housing | |
|---|---|
| Dimensions | Length 70 mm x Width 70 mm x Height 53 mm |
| Weight | 45 g |
| Material | UV-stabilised polycarbonate |
| Protection type | IP20, IP44 depending on cover (order separately) |
| Protection type with accessory | IP44 depending on cover (order separately) |
| Permissible ambient temperature | -25 °C...+50 °C |
| Relative humidity | 5 – 93 %, non-condensing |
| Colour | white, similar to RAL 9010 |
| Electrical version | |
|---|---|
| Control system | KNX |
| Protection class | III |
| Nominal voltage | 29 – 31 V DC |
| Power consumption | 0.2 W |
| Power consumption | 6 mA |
| Sensors | |
|---|---|
| Detection angle | 180° horizontal, 60° vertical |
| Detection range diagonally | Ø 16 m |
| Detection range head-on | Ø 12 m |
| Detection range presence | Ø 8 m |
| Field of detection | up to 101 m² |
| Recommended installation height | 1.1 m |
| Max. mounting height | 2.2 m |
| Level of brightness | 5 – 2000 lx |
| Control | |
|---|---|
| Number of light channels | 2 |
| Number of HVAC-channels | 1 |
| Push button input lighting | 1 |
| Slave input | |
| Mode | Semi-automatic, Fully automatic |
| Switching delay from "dark to light" | 300 s |
| Switching delay from "light to dark" | 30 s |
| Constant light control | |
| Sensitivity configurable | |
| KNX input | manual light control, block objects, slave |
| KNX output | presence, status, light value, HVAC |
| KNX functions | Presence simulation, Manual override, Master- / slave-toiminto, Night-light feature, Sensitivity configurable, Sends a telegram at regular intervals |
| Channels (lighting / HVAC): C1 Lighting | |
|---|---|
| Channel | C1 Lighting |
| Function | Switching, Regulate |
| Switch contact | Bus system |
| Switch-off delay time | 60 s...30 min (adjustable in steps) |
| Orientation light | disabled/0 – 50 %, 2 values can be selected |
| Switch-off delay time, orientation light | 60 s...250 min |
| Channels (lighting / HVAC): C2 Lighting | |
|---|---|
| Channel | C2 Lighting |
| Function | Switching, Regulate |
| Offset setting | c2 offset from c1 (-50 % to +50 %) |
| Switch contact | Bus system |
| Switch-off delay time | 10 s...60 min (adjustable in steps) |
| Orientation light | disabled/0 – 50 %, 2 values can be selected |
| Switch-off delay time, orientation light | 60 s...250 min |
| Channels (lighting / HVAC): C3 HVAC | |
|---|---|
| Channel | C3 HVAC |
| Function | Switching |
| Switch-on delay | 120 s...30 min |
| Switch-off delay time | 10 s...60 min (adjustable in steps) |
| Light and building planning | ||
|---|---|---|
| LDC (EULUMDAT file) | LDT | /products/indoor-automation/presence-and-motion-detectors/compact/ep10426445/download/xom/dbcb6d97-25d2-4c08-a91c-8945857d59e9/ep10426445.ldt?type=1639499290&cHash=96a27872c169fa3db762908b3f128e2c |
| IES | IES | |
| Relux ROLFZ | ROLFZ | |
Planning data BIM | ||