Special Product Features
General Product Features
| General | |
|---|---|
| Device category | Ceiling-mounted presence detector |
| Product information |
Please note the Explanation of circuit breaker in the download area of the product! |
| Included in delivery | Includes lens mask |
| Remote controllable | |
| Conformity | CE, EAC, RoHS, WEEE |
| EU Data-Act betroffen | |
| Warranty | 5 years |
| Mounting | |
|---|---|
| Installation type | Flush-mounted/Device socket Ø 68 mm |
| Installation position | Ceiling |
| Type of connection | Push terminal |
| Connectable wire cross section | 1.5 – 2.5 mm² |
| Housing | |
|---|---|
| Dimensions | Height 70 mm, Ø 108 mm |
| Weight | 153 g |
| Material | UV-stabilised polycarbonate |
| Protection type | IP20 |
| Protection type with accessory | IP54 with surface-mounted box (order separately) |
| Permissible ambient temperature | -25 °C...+50 °C |
| Relative humidity | 5 – 93 %, non-condensing |
| Colour | white, similar to RAL 9010 |
| Electrical version | |
|---|---|
| Control system | 1 – 10 V |
| Protection class | II |
| Nominal voltage | 230 V ~ / 50 Hz |
| In-rush current | 800 A / 200 µs |
| Power consumption | 0.3 W |
| Sensors | |
|---|---|
| Detection angle | 360° |
| Detection range diagonally | 32 m elliptical |
| Detection range head-on | Ø 11 m |
| Field of detection | up to 402 m² |
| Recommended installation height | 3 m |
| Max. mounting height | 10 m |
| Level of brightness | 5 – 2000 lx |
| Control | |
|---|---|
| Number of light channels | 1 |
| Number of HVAC-channels | 1 |
| Push button input lighting | 1 |
| Push button input HVAC | |
| Slave input | |
| Max. number of slave detectors | 10 |
| Mode | Semi-automatic, Fully automatic |
| Switching delay from "dark to light" | 300 s |
| Switching delay from "light to dark" | 30 s |
| Constant light control | |
| Channels (lighting / HVAC): C1 Lighting | |
|---|---|
| Channel | C1 Lighting |
| Function | Switching, Regulate, Dimming |
| Switching capacity |
230 V/50 Hz, 16 AX 2300 W/10 A (cos phi = 1) 1150 VA/5 A (cos phi = 0,5) 600 W LED |
| Switch contact | make contact / non-floating |
| Push button input | |
| Impulse mode | |
| Switch-off delay time | 60 s...15 min (adjustable in steps) |
| Orientation light | 10 % luminous efficiency |
| Switch-off delay time, orientation light | 60 s...60 min |
| Channels (lighting / HVAC): C2 HVAC | |
|---|---|
| Channel | C2 HVAC |
| Function | Switching |
| Switching capacity | 230 V AC/2 A, 24 V DC/2 A, Capacitive load/electronic ballasts max. in-rush current 30 A/20 ms |
| Push button input | |
| Impulse mode | |
| Switch-off delay time | 60 s...120 min (adjustable in steps) |
| Light and building planning | ||
|---|---|---|
| LDC (EULUMDAT file) | LDT | /products/indoor-automation/presence-and-motion-detectors/compact/ep10425783/download/xom/ce67ade8-552e-447f-8a90-016ce0887cc1/ep10425783.ldt?type=1639499290&cHash=befc7a8ad9a11ba1d5955f380c1455eb |
| IES | IES | |
| Relux ROLFZ | ROLFZ | |
Planning data BIM | ||