Change current country? Australia | English Ireland | English Hong | Kong English Singapore | English
Presence and motion detectors | Serie COMPACT

PD-C 180i KNX ECO

Item number EP10426452GTIN 4015120426452

Offers special product features like

  • KNX functions: Twilight switch, motion direction detection function, brightness detection via object, light-dependent motion detection

Technical data

General
Device category Wall-mounted presence detector
Remote controllabledone
Conformity CE, EAC, RoHS, WEEE
 
EU Data-Act betroffendone
Warranty 5 years
Mounting
Installation type Flush-mounted/Device socket Ø 68 mm
Installation position Wall
Installation dimension Installation depth: 25 mm, Ø 60 mm
 
Type of connection Push terminal
Connectable wire cross section 0.6 – 0.8 mm²
Housing
Dimensions Length 70 mm x Width 70 mm x Height 55 mm
Weight 45 g
Material UV-stabilised polycarbonate
Protection type IP20, IP44 depending on cover (order separately)
 
Protection type with accessory IP44 depending on cover (order separately)
Permissible ambient temperature -25 °C...+50 °C
Relative humidity 5 – 93 %, non-condensing
Colour white, similar to RAL 9010
Electrical version
Control system KNX
Protection class III
Nominal voltage 29 – 31 V DC
 
Power consumption 0.2 W
Power consumption 6 mA
Sensors
Detection angle 180° horizontal, 60° vertical
Detection range diagonally Ø 16 m
Detection range head-on Ø 12 m
Detection range presence Ø 8 m
 
Field of detection up to 101 m²
Max. mounting height 2.2 m
Level of brightness 5 – 2000 lx
Control
Number of light channels 2
Push button input lighting 1
Slave inputdone
Mode Semi-automatic, Fully automatic
Switching delay from "dark to light" 300 s
 
Switching delay from "light to dark" 30 s
Sensitivity configurabledone
KNX input manual light control, block objects, slave
KNX output presence, status, light value
KNX functions Manual override, Master- / slave-toiminto, Night-light feature, Sensitivity configurable, Sends a telegram at regular intervals
Channels (lighting / HVAC): C1 Lighting
ChannelC1 Lighting
Function Switching
 
Switch contact Bus system
Switch-off delay time 60 s...30 min (adjustable in steps)
Channels (lighting / HVAC): C2 Lighting
ChannelC2 Lighting
Function Switching
 
Switch contact Bus system
Switch-off delay time 10 s...60 min (adjustable in steps)
All files as ZIP

Downloads