General | |
---|---|
Device category | Wall-mounted presence detector |
Remote controllable |
Conformity | CE, EAC, RoHS, WEEE |
Warranty | 5 years |
Mounting | |
---|---|
Installation type | Flush-mounted/Device socket Ø 68 mm |
Installation position | Wall |
Installation dimension | Installation depth: 25 mm, Ø 60 mm |
Type of connection | Push terminal |
Housing | |
---|---|
Dimensions | Length 70 mm x Width 70 mm x Height/Depth 55 mm |
Weight | 35 g |
Material | UV-stabilised polycarbonate |
Protection type | IP40 |
Protection type with accessory | IP44 depending on cover (order separately) |
Permissible ambient temperature | 5 °C...+50 °C |
Relative humidity | 5 – 93 %, non-condensing |
Colour | white, similar to RAL 9010 |
Electrical version | |
---|---|
Control system | KNX |
Protection class | III |
Nominal voltage | 29 – 31 V DC |
Power consumption | 0.2 W |
Power consumption | 6 mA |
Sensors | |
---|---|
Detection angle | 180° horizontal, 60° vertical |
Detection range diagonally | Ø 16 m |
Detection range head-on | Ø 12 m |
Detection range presence | Ø 8 m |
Field of detection | up to 101 m² |
Recommended installation height | 1.1 m |
Max. mounting height | 2.2 m |
Level of brightness | 5 – 2000 lx |
Control | |
---|---|
Number of light channels | 2 |
Number of HVAC-channels | 1 |
Push button input lighting | 1 |
Push button input HVAC | |
Slave input | |
Mode | Semi-automatic, Fully automatic |
Constant light control | |
Sensitivity configurable | |
KNX input | manual light control, block objects, slave |
KNX output | presence, status, light value, HVAC |
KNX functions | Presence simulation, Manual override, Master- / slave-toiminto, Night-light feature, Sensitivity configurable, Sends a telegram at regular intervals |
Channels (lighting / HVAC): C1 Lighting | |
---|---|
Channel | C1 Lighting |
Function | Switching, Regulate |
Switch contact | Bus system |
Switch-off delay time | 30 s...30 min (adjustable in steps) |
Orientation light | disabled/0 – 50 %, 2 values can be selected |
Switch-off delay time, orientation light | 60 s...250 min |
Channels (lighting / HVAC): C2 Lighting | |
---|---|
Channel | C2 Lighting |
Function | Switching, Regulate |
Offset setting | c2 offset from c1 (-50 % to +50 %) |
Switch contact | Bus system |
Switch-off delay time | 10 s...60 min (adjustable in steps) |
Orientation light | disabled/0 – 50 %, 2 values can be selected |
Switch-off delay time, orientation light | 60 s...250 min |
Channels (lighting / HVAC): C3 HVAC | |
---|---|
Channel | C3 HVAC |
Function | Switching |
Switch-on delay | 120 s...30 min |
Switch-off delay time | 10 s...60 min (adjustable in steps) |
GENERAL | ||
---|---|---|
Data sheet |
Light and building planning | ||
---|---|---|
Planning data BIM |
Installation | ||
---|---|---|
KNX application / software | ZIP | |
Operating instructions | ||
Short instruction |
Tender specifications | ||
---|---|---|
Invitation to tender text neutral (rtf) | RTF | |
Invitation to tender text neutral (x81) | X81 | |
Tender text with leading brand | RTF |