FLAT

PD-FLAT 360i/8 ROUND BLACK KNX

Item number EP10451768

Offers special product features like

  • Presence and daylight dependent constant light control
  • Simple parameterisation, remote control and documentation with ESY-Pen and ESY-App
  • KNX functions: Alarm, twilight switch, brightness detection, light-dependent motion detection, snooze function, scene telegram via object

Shortfacts

Device category Ceiling-mounted presence detector
Included in delivery Includes lens mask
Installation type Flush-mounted/Device socket Ø 68 mm
Installation position Ceiling
Protection type IP20
Dimensions Height/Depth 30 mm, Ø 94 mm
Detection angle 360°
Detection range diagonally Ø 8 m
Field of detection up to 50 m²
Permissible ambient temperature 5 °C...+35 °C
Warranty 5 years

Technical data

General
Device category Ceiling-mounted presence detector
Remote controllabledone
Conformity CE, EAC, RoHS, WEEE
Warranty 5 years
Mounting
Installation type Flush-mounted/Device socket Ø 68 mm
Installation position Ceiling
Installation dimension Installation depth: 24 mm, Ø 60 mm
Type of connection Push terminal
Housing
Dimensions Height/Depth 30 mm, Ø 94 mm
Weight 72.8 g
Material UV-stabilised polycarbonate
Protection type IP20
Permissible ambient temperature 5 °C...+35 °C
Relative humidity 5 – 93 %, non-condensing
Colour black, similar to RAL 9004
Electrical version
Control system KNX
Protection class III
Nominal voltage 29 – 31 V DC
Power consumption 0.2 W
Power consumption 6 mA
Sensors
Detection angle 360°
Detection range diagonally Ø 8 m
Detection range head-on Ø 6 m
Detection range presence Ø 4 m
Field of detection up to 50 m²
Max. mounting height 5 m
Level of brightness 3 – 1000 lx
Control
Number of light channels 2
Number of HVAC-channels 1
Push button input lighting 2
Push button input HVACdone
Slave inputdone
Mode Semi-automatic, Fully automatic
Constant light controldone
KNX input manual light control, block objects, reset, slave
KNX output presence, status, light value, HVAC
KNX functions Presence simulation, Manual override, Master- / slave-toiminto, Night-light feature, Sensitivity configurable, Sends a telegram at regular intervals
Channels (lighting / HVAC)
ChannelC1 Lighting
Function Switching, Regulate
Switch contact Bus system
Switch-off delay time 30 s...720 min (adjustable in steps)
Orientation light disabled/10 – 50 %, 2 values can be selected
Switch-off delay time, orientation light 60 s...240 min
ChannelC2 Lighting
Function Switching, Regulate
Offset setting c2 offset from c1 (-50 % to +50 %)
Switch contact Bus system
Switch-off delay time 10 s...60 min (adjustable in steps)
Orientation light disabled/10 – 50 %, 2 values can be selected
Switch-off delay time, orientation light 60 s...250 min
ChannelC3 HVAC
Function Switching
Switch contact Bus system
Switch-on delay 120 s...30 min
Switch-off delay time 10 s...60 min (adjustable in steps)

Kontakt Sidebar - en-gb

Kontakt Sidebar

CONTACT US

* Required

Similar products

Other Products

SLB

SLBEmergency lights

Mehr

SVENJAWall and ceiling lights

Mehr
SMARTDRIVER

SMARTDRIVERControls

Mehr
FLAT MINI

FLAT MINIBrightness controller

Mehr
STELLA

STELLARecessed lights

Mehr
DIN Rail

DIN RailActuators

Mehr