Offers special product features like
General | |
---|---|
Device category | Outdoor motion detector |
Product information | Please note the Explanation of circuit breaker in the download area of the product! |
Remote controllable |
Conformity | CE, EAC, RoHS, WEEE |
Warranty | 5 years |
Mounting | |
---|---|
Installation type | Surface mounting |
Installation position | Ceiling / wall |
Type of connection | Push terminal |
Housing | |
---|---|
Dimensions | Length 138 mm x Width 92 mm x Height/Depth 107.5 mm |
Weight | 270 g |
Material | UV-resistant plastic |
Protection type | IP55 |
Permissible ambient temperature | -25 °C...+50 °C |
Relative humidity | 10 – 90%, non-condensing |
Impact resistance | IK07 |
Colour | graphite grey, similar to RAL 7024 |
Electrical version | |
---|---|
Control system | ON/OFF |
Protection class | II |
Nominal voltage | 220 – 240 V ~ / 50 – 60 Hz |
In-rush current | 800 A / 200 µs |
Stand-by consumption | < 0.5 W |
Sensors | |
---|---|
Detection angle |
280° (3 x 95° separately adjustable) and 360° creep protection vertically tiltable by +90°/-10° |
Detection range diagonally | Ø 40 m |
Detection range head-on | Ø 10 m |
Detection range creep protection | Ø 4 m |
Field of detection | up to 979 m² |
Range adjustment | Mechanical, electronic |
Recommended installation height | 3 m |
Max. mounting height | 6 m |
Level of brightness | 2 – 2000 lx |
Control | |
---|---|
Number of light channels | 1 |
Push button input lighting | 1 |
Number of parallel switchable detectors | 10 |
Integrated timer |
Channels (lighting / HVAC): C1 Lighting | |
---|---|
Channel | C1 Lighting |
Function | Switching |
Switching capacity |
230 V/50 - 60 Hz 2300 W / 10 A (cos phi = 1), 1150 VA / 5 AX (cos phi = 0,5) 600 W LED |
Switch contact | make contact / non-floating |
Push button input | |
Impulse mode | |
Switch-off delay time | 60 s...240 min (adjustable in steps) |
GENERAL | ||
---|---|---|
Data sheet | ||
Declaration of conformity | ||
Explanation of circuit breaker |
Light and building planning | ||
---|---|---|
Planning data BIM |
Installation | ||
---|---|---|
Operating instructions | ||
Short instruction |
Tender specifications | ||
---|---|---|
Invitation to tender text neutral (rtf) | RTF | |
Invitation to tender text neutral (x81) | X81 | |
Tender text with leading brand | RTF |